The standard values for service illuminance (Em [Lux]), color appearance (F), color rendering group (Ra), and unified glare restriction (UGRL) according to EN 12464-1 are listed in the table for the various types of interior or activity. The ratings for service illuminance, color rendering group, and direct glare restriction class represent minimum values to be met by the lighting system.
Interiors / Activities |
Em[lx] |
F |
Ra |
UGRL |
Waiting rooms, day lounges |
200 |
ww, nw |
80 |
22 |
Corridors: Daylighting |
200 |
ww, nw |
80 |
22 |
Corridors: Night lighting |
50 |
ww, nw |
80 |
22 |
Personal service rooms |
500 |
ww, nw | 80 | 19 |
Staff lounges |
300 |
ww, nw | 80 | 19 |
Bed rooms: Ambient lighting |
100 |
ww, nw | 80 | 19 |
Reading light | 300 |
ww, nw | 80 | 19 |
Treatment rooms | 300 |
ww, nw | 80 | 19 |
General examination and Treatment rooms | 1000 |
ww, nw, tw | 90 |
19 |
Night observation lighting | 5 |
ww, nw | 80 | - |
Washbasin and Toilets |
200 |
ww, nw | 80 | 22 |
General examination and Treatment rooms: Ambient lighting | 500 |
ww, nw, tw | 90 |
19 |
Dressing room |
1000 |
ww, nw, tw | 90 |
19 |
Medicinal baths |
500 |
ww, nw | 80 | 19 |
Massage and Physiotherapy |
300 |
ww, nw | 80 | 19 |
Laboratories: Ambient lighting | 500 |
ww, nw | 80 | 19 |
Color checks | 1000 |
T > 6000 K | 90 |
19 |