The standard values for service illuminance (Em [Lux]), color appearance (F), color rendering group (Ra), and unified glare restriction class (UGRL) according to EN 12464-1 are listed in the table for the various types of interior or activity. The ratings for service illuminance, color rendering group, and direct glare restriction class represent minimum values to be met by the lighting system.


Interiors / Activities

Em[lx]

F

Ra

UGRL

Loading plant

50

ww, nw

20

-

Boiler room, Power house

100

ww, nw

40

28

Pressure suppression chamber (atomic power plant)

200

ww, nw

80

25

Ancillary rooms, e.g. pump rooms, condenser rooms

50

ww, nw

60

25

Indoor switching plant

100

ww, nw

80

16

Control room

300

ww, nw

20

-